Air Changes per Hour and Clearance Time

Air changes per hour from airflow and room size, with CDC's times to remove 99% and 99.9% of an airborne contaminant.

Open the tool → Runs in your browser. Data leaves only if you deliberately send a problem report from the interactive tool.

Example

Airflow unit
CFM (cubic feet per minute)
Supply or exhaust airflow
240
Room unit
Feet (volume in cubic feet)
Room length
12
Room width
10
Room height
10

Result: 12 air changes per hour: about 23.0 minutes to remove 99% and 34.5 minutes to remove 99.9%.

The tool opens with these values already filled in. Replace them with your own.

What you enter

  • Airflow unit: cubic feet per minute (cfm) or cubic meters per hour (m3h)
  • Supply or exhaust airflow
  • Room unit: feet and cubic feet (ft) or meters and cubic meters (m)
  • Room volume (or enter the three dimensions)
  • Room length
  • Room width
  • Room height
  • Required air changes per hour, from your own standard (optional)
How this is calculated

Citation

CDC, Guidelines for Environmental Infection Control in Health-Care Facilities (2003), Appendix B, Table B.1 and its formula (page dated January 11, 2024); FDA, Sterile Drug Products Produced by Aseptic Processing (September 2004), for the 20 air changes reference. Read the sources: CDC Appendix B ↗, FDA 2004 guidance ↗